高電壓測試設備通用技術條件
第8部分:有載分接開關測試儀
Genera technical specifications for high voltage test equipments
Part 8:detector of on-load tap-changers
2004-03-09發(fā)布 2004-06-01實施
中華人民共和國國家發(fā)展和改革委員會 發(fā) 布
目 次
前言··································································································································
1 范圍·····························································································································
2 規(guī)范性引用文件···········································································································
3 術語和定義··················································································································
4 命名和分類··················································································································
5 技術要求······················································································································
6 試驗方法······················································································································
7 檢驗規(guī)則······················································································································
8 標志、包裝、運輸、儲存·····························································································
附錄A(規(guī)范性附錄) 動作時間誤差測量方法···································································
參考文獻···························································································································
前 言
本標準是根據(jù)原國家經(jīng)濟貿易委員會電力司《關于確認1999年度電力行業(yè)標準制、修訂計劃項目的通知》(電力[2000]22號)下達的《高電壓測試儀器通用技術條件》標準項目的制定任務安排制定的。
DL/TT846《高電壓測試儀器通用技術條件》是一個系列標準,本次發(fā)布9個部分:
——第1部分:高電壓分壓器測量系統(tǒng);
——第2部分:沖擊電壓測量系統(tǒng);
——第3部分:高壓開關綜合測試儀;
——第4部分:局部放電測量儀;
——第5部分:六氟化硫微量水分儀;
——第6部分:六氟化硫氣體檢漏儀;
——第7部分:絕緣油介電強度測試儀;
——第8部分:有載分接開關測試儀;
——第9部分:真空開關真空度測試儀。
本部分是DL/TT846《高電壓測試儀器通用技術條件》的第8部分。
本部分的附錄A為規(guī)范性附錄。
本部分由中國電力企業(yè)聯(lián)合會提出。
本部分由全國高壓電氣安全標準化技術委員會歸口。
本部分負責起草單位:武漢高壓研究所。
本部分參加起草單位:浙江省電力試驗研究所、河北省保定市精藝電子儀器有限公司。
本部分起草人:蔡崇積、詹洪炎、張正平、張瑞生。
本部分委托武漢高壓研究所負責解釋。
高電壓測試設備通用技術條件
第8部分:有載分接開關測試儀
1 范圍
DL/T846的本標準規(guī)定了電力變壓器有載分接(有載調壓)開關測試儀的產品技術要求、試驗方法、檢驗規(guī)則和產品標志、包裝、運輸、儲存。
本標準適用于電力變壓器有載分接(有載調壓)開關測試儀(以下簡稱測試儀)的生產和大修。
2 規(guī)范性弓廠用文件
下列文件中的條款通過DL/T 846的本部分的引用而成為本部分的條款。凡是注日期的引用文件,其隨后所有的修改單(不包括勘誤的內容)或修訂版均不適用于本部分,然而,鼓勵根據(jù)本部分達成協(xié)議的各方研究是否可使用這些文件的最新版本。凡是不注日期的引用文件,一其最新版本適用于本部分。
GBl91 包裝儲運圖示標志EQV ISO 780:1997
GB/T 6587.1—1986 電子測量儀器環(huán)境試驗總綱
GB/T 6587.2 電子測量儀器溫度試驗
GB/T 6587.3 電子測量儀器濕度試驗
GB/T 6587.4 電子測量儀器振動試驗
GB/T 6587.5 電子測量儀器沖擊試驗
GB/T6587.6 電子測量儀器運輸試驗
GB/T 6587.7 電子測量儀器基本安全試驗
GB/T 6587.8 電子測量儀器電源頻率與電壓試驗
GB/T 6593 電子測量儀器質量檢驗規(guī)則
GB/T 11463—1989 電子測量儀器可靠性試驗
3 術語和定義
下列術語和定義適用DL/T 846的本標準。
3.1
有載分接開關 on-load tap-changers
能在變壓器勵磁或負載狀態(tài)下進行操作,用以調換線圈的分接連接位置改變電力系統(tǒng)運行電壓的一種裝置。在電力系統(tǒng)中也稱這種裝置為有載調壓開關。
3.2
過渡電阻 transition esistance
由一個或幾個單元組成的電阻器,橋接于正在使用的分接頭和將要使用的分接頭上,以達到將負載電流無間斷地或無顯著變化地從一個分接轉到另一個分接的目的。與此同時,在兩個分接頭被跨接的期間限制其循環(huán)電流。
3.3
切換時間 switch time
轉換開關從一個分接切換到另一個分接的輔助觸頭所需的時間。
3.4
動作順序 unning order
分接開關操作機構從一個分接切換到另一個分接所需的圈數(shù),以及分接開關操作機構從第一個接切換到最后一個分接動作過程。
4 命名和分類
4.1 型號命名
型號用有載兩字的拼音第一個字母YZ作首位,方框內可以用拼音字母、英文26個字母及0~9的數(shù)字命名。
4.2 類別
不帶線圈測量有載分接開關特性的測試儀為A類,帶線圈測量有載分接開關特性的測試儀為B類,不帶線圈和帶線圈均能測量有載分接開關特性的測試儀為C類,變壓器無中心點引出也能測量有載分接開關特性的測試儀為D類。
5 技術要求
5.1 使用條件
a)環(huán)境溫度:0℃~+40℃;
b)環(huán)境相對濕度:不大于80%;
c)電源電壓:220V±22V;
d)電源頻率:50Hz±1Hz。
5.2 外觀
測試儀表面無明顯劃痕、裂紋和變形,金屬件無銹蝕,功能鍵操作靈活無卡澀,各引出端鈕和功能按鍵應有明確、清晰的標注,測試儀應有明顯的接地端鈕。
5.3 絕緣性能
5.3.1 絕緣電阻
電源輸入端對機殼的絕緣電阻應大于2MΩ。
5.3.2 絕緣強度
測試儀電源輸入端對機殼應能耐受1500V、歷時1min的工頻耐壓,無擊穿和飛弧現(xiàn)象。
5.4 恒壓源
測試儀內部恒壓源的電壓穩(wěn)定度應優(yōu)于l×l0-3,紋波系數(shù)優(yōu)于1.0%,輸出電壓不低于20V。
5.5 恒流源
測試儀內部恒流源的電流穩(wěn)定度應優(yōu)于l×l0-3,紋波系數(shù)優(yōu)于1.0%,輸出電流不低于lA,開口電壓不低于20V。
5.6 過渡電阻測量
過渡電阻的測量范圍0.1Ω~20Ω,分辨率為0.01Ω,過渡電阻在0.lΩ~lΩ的范圍內最大允許偏差優(yōu)于±0.1Ω;在1Ω~20Ω(不含1Ω)的范圍內最大允許偏差優(yōu)于±1.0%。
5.7 動作時間測量
動作時間的測量范圍lms~250ms,分辨率為0.1ms。動作時間在1ms~100ms范圍內允許偏差優(yōu)于±1ms;動作時間在100ms~250ms(不含100ms)內,最大允許偏差優(yōu)于±1%。
5.8 動作順序測量
動作順序的測量范圍0~50圈,每圈為360º,分辨率為1º,最大允許偏差在±3º及以上。
5.9 環(huán)境條件
應滿足GB/T 6587.1—1986第II組的要求。
5.10 可靠性
測試儀的平均無故障時間應不小于1500h。
6 試驗方法
6.1 試驗條件
a)環(huán)境溫度:20℃±5℃;
b)環(huán)境相對濕度:40%~75%;
c)電源頻率:50Hz±0.5Hz;
d)電源電壓:220×(l±5%)V。
6.2 試驗設備
6.2.1 直流電壓表
5位半直流數(shù)字電壓表,準確度等級為0.02級。
6.2.2 信號發(fā)生器
輸出電壓不小于5V,頻率穩(wěn)定度l×10-5,輸出波形寬度可任意調整。
6.2.3 示波器
采樣頻率100Mhz,準確度等級為2級。
6.2.4 標準電阻器
阻值為0.lΩ~20Ω的標準電阻一組,準確度等級為0.1級。
6.2.5 絕緣電阻表
電壓等級為500V,測量范圍為0.2MΩ~500MΩ。
6.2.6 交流耐壓器
輸出電壓為2000V,準確度等級為3級。
6.2.7 圓周運動標準器
準確度為0.5級。
6.3 外觀檢查
用目測的方法檢查,應滿足5.2的規(guī)定。
6.4 絕緣性能測試
6.4.1 絕緣電阻
用500V絕緣電阻表測量電源輸入端對機殼的絕緣電阻,應滿足5.3.1的規(guī)定。
6.4.2 絕緣強度
用2000V交流工頻耐壓器在電源輸入端對機殼施加1500V電壓、歷時lmin,應滿足5.3.2的規(guī)定。
6.5 恒壓源測試
測試儀在正常工作狀態(tài)下,用數(shù)字電壓表測量每相恒壓源電壓,并進行10min的穩(wěn)定度測量,后每組輸出之間接一只標準電阻器,用示波器測量電源輸出波形。紋波系數(shù)按式(1)進行計算:
(1)
式中:
——紋波系數(shù);
——峰峰電壓值,V;
U——直流電壓值,V。
測量結果應滿足5.4的規(guī)定
6.6 恒流源測試
測試儀在正常工作狀態(tài)下,每相輸出之間接一只標準電阻器,用示波器測量電源輸出波形,用數(shù)字電壓表測量標準電阻兩端電壓,并進行l(wèi)0min的穩(wěn)定度測量。電流按式(2)進行計算:
(2)
式中:
——恒流源輸出電流,A
——標準電阻,Ω;
——標準電阻兩端電壓,V。
測量結果應滿足5.5的規(guī)定。
6.7 過渡電阻測量誤差試驗
用標準電阻器作為被試對象,測試儀對標準電阻進行測試,測試點應有10個點,過渡電阻在0.1Ω~1Ω1Q的范圍內測量誤差按式(3)計算:
(3)
式中:
——電阻測量誤差,Ω;
——儀器的測量值,Ω;
——標準電阻值,Ω。
過渡電阻在1Ω~20Ω(不含1Ω)的范圍內測量誤差按式(4)計算:
(4)
式中:
——電阻測量誤差,Ω;
——儀器的測量值,Ω;
——標準電阻值,Ω。
測量結果應滿足5.6的規(guī)定。
6.8 動作時間測量誤差試驗
測試儀的三個通道分別測量信號發(fā)生器提供的標準方波,測量接線方法見附錄A。時間寬度按10ms~100ms和100ms~250ms分段進行測量,每段測試點應有10個點。1ms~100ms段的測量誤差按式(5)計算:
(5)
式中:
——動作時間測量差,ms;
——測試儀器量值,ms;
——標準時間,ms。
在100ms~250ms(不含100ms)段的測量誤差按式(6)計算;
(6)
式中:
——動作時間測量差,ms;
——測試儀器量值,ms;
——標準時間,ms。
兩段測試結果應滿足5.7的規(guī)定。
6.9 動作順序測量
將測量圓盤和傳感器固定在標準的圓周運動臺上,通過圓周運動檢驗圓盤、傳感器和測量回路組成 系統(tǒng)誤差。誤差按 (7)計算:
(7)
式中:
——儀器測量誤差;
——儀器測量值;
——儀器標準值。
測量結果應滿足5.8的規(guī)定。
6.10 環(huán)境試驗
環(huán)境試驗按GB/T6587.1––1986第II組要求進行試驗。
6.10.1 溫度試驗
按GB/T6587.2的方法進行溫度試驗,同時按GB/T6587.8的要求加入儀器電源頻率與電壓變化率試驗,并滿足標準要求。
6.10.2 濕度試驗
按GB/T6587.3的方法進行濕度試驗,同時按GB/T6587.7的要求加入儀器基本安全試驗,并滿足標準要求。
6.10.3 振動試驗
按GB/T6587.4的方法進行振動試驗,并滿足標準要求。
6.10.4 沖擊試驗
按GB/T 6587.5的方法進行沖擊試驗,并滿足標準要求。
6.10.5 運輸試驗
按GB/T6587.6的萬法進行運輸試驗,并滿足標準要求。
6.11 可靠性試驗
按GB11463—1989表1定時定數(shù)截尾試驗方案1.1的規(guī)定進行,并滿足標準要求。
7 檢驗規(guī)則
7.1 檢驗分類
檢驗分為型式試驗、出廠檢驗、常規(guī)檢驗。
7.2 檢驗項目
檢驗項目見表1。
表1 檢驗項目表
序號 |
檢測項目 |
型式檢驗 |
出廠檢驗 |
常規(guī)檢驗 |
1 |
外觀檢查 |
√ |
√ |
√ |
2 |
絕緣電阻 |
√ |
√ |
√ |
3 |
絕緣強度 |
√ |
√ |
√ |
4 |
恒壓源檢驗 |
√ |
√ |
○ |
5 |
恒流源檢驗 |
√ |
√ |
○ |
6 |
過渡電阻測量誤差檢驗 |
√ |
√ |
√ |
7 |
動作時間測量誤差檢驗 |
√ |
√ |
√ |
8 |
動作順序測量誤差檢驗 |
√ |
√ |
√ |
9 |
溫度試驗 |
√ |
○ |
○ |
10 |
濕度試驗 |
√ |
○ |
○ |
11 |
振動試驗 |
√ |
○ |
○ |
12 |
沖擊試驗 |
√ |
○ |
○ |
13 |
運輸試驗 |
√ |
○ |
○ |
14 |
電源頻率與電壓變化試驗 |
√ |
○ |
○ |
15 |
基本安全試驗 |
√ |
○ |
○ |
16 |
可靠性試驗 |
√ |
○ |
○ |
注:√為必須做試驗項目;○為不做的試驗項目。 |
7.3 型式試驗
型式試驗的目的在于檢驗產品設計的合理性和在本技術條件下的適應性。
7.4 出廠檢驗
出廠檢驗的目的在于檢驗測試儀制造過程中的缺陷和測試儀的測量準確度,測試儀內部電源的可靠性。
7.5 常規(guī)檢驗
測試儀所測數(shù)據(jù)直接影響電力系統(tǒng)的安全運行,使用中的測試儀必須每年檢一次,保證測試儀測量準確可靠。
7.6 抽樣方法和要求
抽樣方法必須滿足GB/T6593的要求。在下列情況之一,必須進行型式試驗:
a)新產品研制時進行,以后每三年進行一次;
b)在生產中有設計、材料、工藝或結構等改變,且其改變可能影響產品性能時;
c)停產一年以上恢復生產時;
d)國家質量監(jiān)督機構要求進行質量一致性的檢驗時。
7.7 合枯判定規(guī)則
合格判定規(guī)則為:
a)樣品經(jīng)過型式檢驗,末發(fā)現(xiàn)主要缺陷,則判定產品合格。檢驗中如發(fā)現(xiàn)有一個主要缺陷,則進行第二次抽樣,重復進行型式檢驗。如未發(fā)現(xiàn)主要缺陷,仍判定該測試儀本次型式檢驗合格。如第二次抽樣樣品仍存在主要缺陷,則判定本次型式檢驗不合格。
b)檢驗結果達不到5章要求的任一條時,均按存在主要缺陷判定。
c)檢驗中測試儀樣品出現(xiàn)故障后允許進行修復,修復內容如對己做出檢驗的項目的檢驗結果沒有影響,可以繼續(xù)往下進行檢驗。反之,受影響的檢驗項目應重做。
8 標志、包裝、運輸、儲存
8.l 標志
產品銘牌應有下列明顯標志:
a)產品名稱;
b)產品型號;
c)出廠編號;
d)出廠年月;
e)制造廠名;
f)測量范圍;
g)準確度等級;
h)生產許可證標志和編號。
8.2 包裝
包裝應符合GBl91的有關標志的規(guī)定,并標明“小心輕放”、“向上”,“防雨”等標志。
8.3 運輸
產品應適于陸運、空運、水運 (海運),運輸裝卸按包裝箱上的標志進行操作。
8.4 儲存
包裝完好的測試儀應滿足GB 191中條款規(guī)定的儲存運輸要求,長期不用的測試儀應保留原包裝,在相對濕度不大于80% 庫房內儲存,室內無酸、堿、鹽及腐蝕性、爆炸性氣體和灰塵以及雨、雪的侵害。
附錄A
(規(guī)范性附錄)
動作時間誤差測量方法
由于信號發(fā)生器輸出容量小,可能無法直接驅動被測儀器,所以必須在信號發(fā)生器與測試儀之間加一個電子模擬開關進行測試,所以信號為方波,接線方法見圖A.1。
圖A.1 動作時間測量誤差檢測接線方法
參 考 文 獻
GB 10230—1988 有載分接開在 EQV IEC60214:1989
DL/T 574—1995 有載分妝開關運行維修導則
JB/T 8314—1996 有載分妝開關試驗導則
|